SECTION 410 - MEDICAL GAS SYSTEMS IN GROUPS B AND I OCCUPANCIES

Medical gas systems in Groups B and I Occupancies shall be installed and maintained in accordance with this section and the Fire Code. When nonflammable gas cylinders for such systems are located inside buildings, they shall be in a separate room or enclosure separated from the rest of the building by not less than one-hour fire-resistive construction. Doors to the room or enclosure shall be self-closing smoke- and draft-control assemblies having a fire-protection rating of not less than one hour. Rooms shall have at least one exterior wall in which there are not less than two vents of not less than 36 square inches (0.023 m²) in area per vent. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling.

EXCEPTION: When an exterior wall cannot be provided for the room, automatic sprinklers shall be installed within the room and the room shall be vented to the exterior through ducting contained within a one-hour-rated shaft enclosure. Approved mechanical ventilation shall provide six air changes per hour for the room.