SECTION 708 - FIRE BLOCKS AND DRAFT STOPS

708.1 General. In combustible construction, fireblocking and draftstopping shall be installed to cut off all concealed draft openings (both vertical and horizontal) and shall form an effective barrier between floors, between a top story and a roof or attic space, and shall subdivide attic spaces, concealed roof spaces and floor-ceiling assemblies. The integrity of all fire blocks and draft stops shall be maintained.

708.2 Fire Blocks.

708.2.1 Where required. Fireblocking shall be provided in the following locations:

1. In concealed spaces of stud walls and partitions, including furred spaces, at the ceiling and floor levels and at 10-foot (3048 mm) intervals both vertical and horizontal. See also Section 803, Item 1.

EXCEPTION: Fire blocks may be omitted at floor and ceiling levels when approved smoke-actuated fire dampers are installed at these levels.

2. At all interconnections between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings and cove ceilings.

3. In concealed spaces between stair stringers at the top and bottom of the run and between studs along and in line with the run of stairs if the walls under the stairs are unfinished.

4. In openings around vents, pipes, ducts, chimneys, fireplaces and similar openings which afford a passage for fire at ceiling and floor levels, with noncombustible materials.

5. At openings between attic spaces and chimney chases for factory-built chimneys.

6. Where wood sleepers are used for laying wood flooring on masonry or concrete fire-resistive floors, the space between the floor slab and the underside of the wood flooring shall be filled with noncombustible material or fire blocked in such a manner that there will be no open spaces under the flooring which will exceed 100 square feet (9.3 m²) in area and such space shall be filled solidly under all permanent partitions so that there is no communication under the flooring between adjoining rooms.

EXCEPTIONS: 1. Fire blocking need not be provided in such floors when at or below grade level in gymnasiums.

2. Fire blocking need be provided only at the juncture of each alternate lane and at the ends of each lane in a bowling facility.

708.2.2 Fire block construction. Except as provided in Item 4 above, fireblocking shall consist of 2 inches (51 mm) nominal lumber or two thicknesses of 1-inch (25 mm) nominal lumber with broken lap joints or one thickness of 23/32-inch (18.3 mm) wood structural panel with joints backed by 23/32-inch (18.3 mm) wood structural panel or one thickness of 3/4-inch (19.1 mm) Type 2-M particleboard with joints backed by 3/4-inch (19.1 mm) Type 2-M particleboard.

Fire blocks may also be of gypsum board, cement asbestos board, mineral fiber, glass fiber or other approved materials securely fastened in place. Loose-fill insulation material shall not be used as a fire block unless specifically fire tested.

Walls having parallel or staggered studs for sound-transmission control shall have fire blocks of mineral fiber or glass fiber or other approved nonrigid materials.

708.3 Draft Stops.

708.3.1 Where required. Draftstopping shall be provided in the locations set forth in this section.

708.3.1.1 Floor-ceiling assemblies.

708.3.1.1.1 Single-family dwellings. When there is usable space above and below the concealed space of a floor-ceiling assembly in a single-family dwelling, draft stops shall be installed so that the area of the concealed space does not exceed 1,000 square feet (93 m²). Draftstopping shall divide the concealed space into approximately equal areas.

708.3.1.1.2 Two or more dwelling units and hotels. Draft stops shall be installed in floor-ceiling assemblies of buildings having more than one dwelling unit and in hotels. Such draft stops shall be in line with walls separating individual dwelling units and guest rooms from each other and from other areas.

708.3.1.1.3 Other uses. Draft stops shall be installed in floor-ceiling assemblies of buildings or portions of buildings used for other than dwelling or hotel occupancies so that the area of the concealed space does not exceed 1,000 square feet (93 m²) and so that the horizontal dimension between stops does not exceed 60 feet (18 288 mm).

EXCEPTION: Where approved automatic sprinklers are installed within the concealed space, the area between draft stops may be 3,000 square feet (279 m²) and the horizontal dimension may be 100 feet (30 480 mm).

708.3.1.2 Attics.

708.3.1.2.1 Two or more dwelling units and hotels. Draft stops shall be installed in the attics, mansards, overhangs, false fronts set out from walls and similar concealed spaces of buildings containing more than one dwelling unit and in hotels. Such draft stops shall be above and in line with the walls separating individual dwelling units and guest rooms from each other and from other uses.

EXCEPTIONS: 1. Draft stops may be omitted along one of the corridor walls, provided draft stops at walls separating individual dwelling units and guest rooms from each other and from other uses, extend to the remaining corridor draft stop.

2. Where approved sprinklers are installed, draftstopping may be as specified in the exception to Section 708.3.1.2.2 below.

708.3.1.2.2 Other uses. Draft stops shall be installed in attics, mansards, overhangs, false fronts set out from walls and similar concealed spaces of buildings having uses other than dwellings or hotels so that the area between draft stops does not exceed 3,000 square feet (279 m²) and the greatest horizontal dimension does not exceed 60 feet (18 288 mm).

EXCEPTION: Where approved automatic sprinklers are installed, the area between draft stops may be 9,000 square feet (836 m²) and the greatest horizontal dimension may be 100 feet (30 480 mm).

708.3.1.3 Draft stop construction. Draftstopping materials shall not be less than 1/2-inch (12.7 mm) gypsum board, 3/8-inch (9.5 mm) wood structural panel, 3/8-inch (9.5 mm) Type 2-M particleboard or other approved materials adequately supported.

Openings in the partitions shall be protected by self-closing doors with automatic latches constructed as required for the partitions.

Ventilation of concealed roof spaces shall be maintained in accordance with Section 1505.

708.4 Draft Stops or Fire Blocks in Other Locations. Fireblocking of veneer on noncombustible walls shall be in accordance with Section 708.2.1, Item 1, above.

For fireblocking ceilings applied against noncombustible construction, see Section 803, Item 1.