Every portion of a Group H Occupancy having a floor
area of 200 square feet (18.58 ) or more
shall be served by at least two separate exits.
EXCEPTION: Group H, Division
4 Occupancies having a floor area of less than 1,000 square feet
(92.9 ) may have one exit.
Within Group H, Divisions 1, 2 and 3 Occupancies, all portions of any room shall be within 75 feet (22 860 mm) of an exit door. Exit doors from a room classified as Group H, Divisions 1, 2 and 3 Occupancies shall not be provided with a latch or lock unless it is panic hardware.
Doors leading to a corridor of fire-resistive construction
shall have a minimum three-fourths-hour fire-protection rating;
shall not have more than 100 square inches (0.0645 )
of wired glass set in steel frames; shall be maintained self-closing
or shall be automatic closing as defined in Section 713.2;
and shall open in the direction of exit travel.
Within Group H, Division 7 and within fabrication
areas of Group H, Division 6 Occupancies, the distance of travel
to an exterior exit door, exit corridor, horizontal exit, exit
passageway or an enclosed stairway shall not exceed 100 feet (30
480 mm).