SECTION 1508 - VALLEY FLASHING

1508.1 Valleys. Roof valley flashings shall be as in this subsection. Shingle application shall be consistent with applicable Table 15-B-1, 15-B-2, 15-D-1 or 15-D-2.

1508.2 Asphalt Shingles. The roof valley flashing shall be provided of not less than 0.016 inch (0.41 mm) (No. 28 galvanized sheet gage) corrosion-resistant metal, and shall extend at least 8 inches (203 mm) from the center line each way. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). Alternatively, the valley shall consist of woven asphalt shingles applied in accordance with manufacturer's printed instructions.

In each case, the roof valley flashing shall have a 36-inch-wide (914 mm) underlayment directly under it consisting of one layer of Type 15 felt running the full length of the valley, in addition to the underlayment specified in Table 15-B-1. In severe climates, the metal valley flashing underlayment shall be solid cemented to the roof underlayment for slopes under 7 units vertical in 12 units horizontal (58.3% slope).

1508.3 Metal Shingles. The roof valley flashing shall be provided of not less than 0.016 inch (0.41 mm) (No. 28 galvanized sheet gage) corrosion-resistant metal, which shall extend at least 8 inches (203 mm) from the center line each way and shall have a splash diverter rib not less than 3/4 inch (19 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). The metal valley flashing shall have a 36-inch-wide (914 mm) underlayment directly under it consisting of one layer of Type 15 felt running the full length of the valley, in addition to underlayment required for metal shingles. In severe climates, the metal valley flashing underlayment shall be solid cemented to the roofing underlayment for roof slopes under 7 units vertical in 12 units horizontal (58.3% slope).

1508.4 Asbestos-cement Shingles, Slate Shingles, and Clay and Concrete Tile. The roof valley flashing shall be provided of not less than 0.016 inch (0.41 mm) (No. 28 galvanized sheet gage) corrosion-resistant metal, which shall extend at least 11 inches (279 mm) from the center line each way and shall have a splash diverter rib not less than 1 inch (25 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of 3 units vertical in 12 units horizontal (25% slope) and over, the metal valley flashing shall have a 36-inch-wide (914 mm) underlayment directly under it consisting of one layer of Type 15 felt running the full length of the valley, in addition to the underlayment specified in Tables 15-D-1 and 15-D-2. In severe climates, the metal valley flashing underlayment shall be solid cemented to the roofing underlayment for slopes under 7 units vertical in 12 units horizontal (58.3% slope).

1508.5 Wood Shingles and Wood Shakes. The roof valley flashing shall be provided of not less than 0.016 inch (0.41 mm) (No. 28 galvanized sheet gage) corrosion-resistant metal, which shall extend at least 8 inches (203 mm) from the center line each way for wood shingles and 11 inches (279 mm) from the center line each way for wood shakes. Sections of flashing shall have an overlap of not less than 4 inches (102 mm). The metal valley flashing shall have a 36-inch-wide (914 mm) underlayment directly under it consisting of one layer of Type 15 felt running the full length of the valley, in addition to underlayment specified in Table 15-B-2. In severe climates, the metal valley flashing underlayment shall be solid cemented to the roofing underlayment for roof slopes under 7 units vertical in 12 units horizontal (58.3% slope).

EXCEPTION: Where local practice indicates satisfactory performance, the building official may permit valley flashing without underlayment.