SECTION 1808 - SPECIFIC PILE REQUIREMENTS

1808.1 Round Wood Piles.

1808.1.1 Material. Except where untreated piles are permitted, wood piles shall be pressure treated. Untreated piles may be used only when it has been established that the cutoff will be below lowest groundwater level assumed to exist during the life of the structure.

1808.1.2 Allowable stresses. The allowable unit stresses for round wood piles shall not exceed those set forth in Table 23-I-E.

The allowable values listed in Table 23-I-E for compression parallel to the grain at extreme fiber in bending are based on load sharing as occurs in a pile cluster. For piles which support their own specific load, a safety factor of 1.25 shall be applied to compression parallel to the grain values and 1.30 to extreme fiber in bending values.

1808.2 Uncased Cast-in-place Concrete Piles.

1808.2.1 Material. Concrete piles cast in place against earth in drilled or bored holes shall be made in such a manner as to ensure the exclusion of any foreign matter and to secure a full-sized shaft. The length of such pile shall be limited to not more than 30 times the average diameter. Concrete shall have a specified compressive strength of not less than 2,500 psi (17.24 MPa).

EXCEPTION: The length of pile may exceed 30 times the diameter provided the design and installation of the pile foundation is in accordance with an approved investigation report.

1808.2.2 Allowable stresses. The allowable compressive stress in the concrete shall not exceed 0.33. The allowable compressive stress of reinforcement shall not exceed 34 percent of the yield strength of the steel or 25,500 psi (175.7 MPa).

1808.3 Metal-cased Concrete Piles.

1808.3.1 Material. Concrete used in metal-cased concrete piles shall have a specified compressive strength of not less than 2,500 psi (17.24 MPa).

1808.3.2 Installation. Every metal casing for a concrete pile shall have a sealed tip with a diameter of not less than 8 inches (203 mm).

Concrete piles cast in place in metal shells shall have shells driven for their full length in contact with the surrounding soil and left permanently in place. The shells shall be sufficiently strong to resist collapse and sufficiently watertight to exclude water and foreign material during the placing of concrete.

Piles shall be driven in such order and with such spacing as to ensure against distortion of or injury to piles already in place. No pile shall be driven within four and one-half average pile diameters of a pile filled with concrete less than 24 hours old unless approved by the building official.

1808.3.3 Allowable stresses. Allowable stresses shall not exceed the values specified in Section 1808.2.2, except that the allowable concrete stress may be increased to a maximum value of 0.40 for that portion of the pile meeting the following conditions:

1. The thickness of the metal casing is not less than 0.068 inch (1.73 mm) (No. 14 carbon sheet steel gage).

2. The casing is seamless or is provided with seams of equal strength and is of a configuration which will provide confinement to the cast-in-place concrete.

3. The specified compressive strength shall not exceed 5,000 psi (34.47 MPa) and the ratio of steel minimum specified yield strength to concrete specified compressive strength shall not be less than 6.

4. The pile diameter is not greater than 16 inches (406 mm).

1808.4 Precast Concrete Piles.

1808.4.1 Materials. Precast concrete piles shall have a specified compressive strength of not less than 3,000 psi (20.68 MPa), and shall develop a compressive strength of not less than 3,000 psi (20.68 MPa) before driving.

1808.4.2 Reinforcement ties. The longitudinal reinforcement in driven precast concrete piles shall be laterally tied with steel ties or wire spirals. Ties and spirals shall not be spaced more than 3 inches apart (76 mm), center to center, for a distance of 2 feet (610 mm) from the ends and not more than 8 inches (203 mm) elsewhere. The gage of ties and spirals shall be as follows:

For piles having a diameter of 16 inches (406 mm) or less, wire shall not be smaller than 0.22 inch (5.6 mm) (No. 5 B.W. gage).

For piles having a diameter of more than 16 inches (406 mm) and less than 20 inches (508 mm), wire shall not be smaller than 0.238 inch (6.0 mm) (No. 4 B.W. gage).

For piles having a diameter of 20 inches (508 mm) and larger, wire shall not be smaller than1/4 inch (6.4 mm) round or 0.259 inch (6.6 mm) (No. 3 B.W. gage).

1808.4.3 Allowable stresses. Precast concrete piling shall be designed to resist stresses induced by handling and driving as well as by loads. The allowable stresses shall not exceed the values specified in Section 1808.2.2.

1808.5 Precast Prestressed Concrete Piles (Pretensioned).

1808.5.1 Materials. Precast prestressed concrete piles shall have a specified compressive strength of not less than 5,000 psi (34.48 MPa) and shall develop a compressive strength of not less than 4,000 psi (27.58 MPa) before driving.

1808.5.2 Reinforcement. The longitudinal reinforcement shall be high-tensile seven-wire strand. Longitudinal reinforcement shall be laterally tied with steel ties or wire spirals.

Ties or spiral reinforcement shall not be spaced more than 3 inches (76 mm) apart center to center for a distance of 2 feet (610 mm) from the ends and not more than 8 inches (203 mm) elsewhere.

At each end of the pile, the first five ties or spirals shall be spaced 1 inch (25 mm) center to center.

For piles having a diameter of 24 inches (610 mm) or less, wire shall not be smaller than 0.22 inch (5.6 mm) (No. 5 B.W. gage). For piles having a diameter greater than 24 inches (610 mm) but less than 36 inches (914 mm), wire shall not be smaller than 0.238 inch (6.0 mm) (No. 4 B.W. gage). For piles having a diameter greater than 36 inches (914 mm), wire shall not be smaller than 1/4 inch (6.4 mm) round or 0.259 inch (6.6 mm) (No. 3 B.W. gage).

1808.5.3 Allowable stresses. Precast prestressed piling shall be designed to resist stresses induced by handling and driving as well as by loads. The effective prestress in the pile shall not be less than 400 psi (2.76 MPa) for piles up to 30 feet (9144 mm) in length, 550 psi (3.79 MPa) for piles up to 50 feet (15 240 mm) in length, and 700 psi (4.83 MPa) for piles greater than 50 feet (15 240 mm) in length.

The compressive stress in the concrete due to externally applied load shall not exceed:

WHERE:

= effective prestress stress on the gross section.

Effective prestress shall be based on an assumed loss of 30,000 psi (206.85 MPa) in the prestressing steel. The allowable stress in the prestressing steel shall not exceed the values specified in Section 1918.

1808.6 Structural Steel Piles.

1808.6.1 Material. Structural steel piles, steel pipe piles and fully welded steel piles fabricated from plates shall conform to U.B.C. Standard 22-1 and be identified in accordance with Section 2202.2.

1808.6.2 Allowable stresses. The allowable axial stresses shall not exceed 0.35 of the minimum specified yield strength or 12,600 pounds per square inch (86.88 MPa), whichever is less.

EXCEPTION: When justified in accordance with Section 1807.11, the allowable axial stress may be increased above 12,600 psi (86.88 MPa) and 0.35, but shall not exceed 0.5.

1808.6.3 Minimum dimensions. Sections of driven H-piles shall comply with the following:

1. The flange projection shall not exceed 14 times the minimum thickness of metal in either the flange or the web, and the flange widths shall not be less than 80 percent of the depth of the section.

2. The nominal depth in the direction of the web shall not be less than 8 inches (203 mm).

3. Flanges and webs shall have a minimum nominal thickness of 3/8 inch (9.5 mm).

Sections of driven pipe piles shall have an outside diameter of not less than 10 inches (254 mm) and a minimum thickness of not less than 1/4 inch (6.4 mm).

1808.7 Concrete-filled Steel Pipe Piles.

1808.7.1 Material. The concrete-filled steel pipe piles shall conform to U.B.C. Standard 22-1 and shall be identified in accordance with Section 2202.2. The concrete-filled steel pipe piles shall have a specified compressive strength of not less than 2,500 psi (17.24 MPa).

1808.7.2 Allowable stresses. The allowable axial stresses shall not exceed 0.35 of the minimum specified yield strength of the steel plus 0.33 of the specified compressive strength of concrete, provided shall not be assumed greater than 36,000 psi (248.22 MPa) for computational purposes.

EXCEPTION: When justified in accordance with Section 2807.11, the allowable stresses may be increased to 0.50 .

1808.7.3 Minimum dimensions. Driven piles of uniform section shall have a nominal outside diameter of not less than 8 inches (203 mm).