2322.1 Structural Floor Sheathing. Structural floor sheathing shall be designed in accordance with the general provisions of this code and the special provisions in this section.

Sheathing used as subflooring shall be designed to support all loads specified in this code and shall be capable of supporting concentrated loads of not less than 300 pounds (1334 N) without failure. The concentrated load shall be applied by a loaded disc, 3 inches (76 mm) or smaller in diameter.

Flooring, including the finish floor, underlayment and subfloor, where used, shall meet the following requirements:

Deflection under uniform design load limited to 1/360 of the span between supporting joists or beams.

Deflection of flooring relative to joists under a 1-inch-diameter (25 mm) concentrated load of 200 pounds (890 N) limited to 0.125 inch (3.2 mm) or less when loaded midway between supporting joists or beams not over 24 inches (610 mm) on center and 1/360 of the span for spans over 24 inches (610 mm).

Floor sheathing conforming to the provisions of Table 23-I-R-1, 23-I-R-2, 23-I-S-1, 23-I-T-1 or 23-I-T-2 shall be deemed to meet the requirements of this subsection.

2322.2 Structural Roof Sheathing. Structural roof sheathing shall be designed in accordance with the general provisions of this code and the special provisions in this section. Structural roof sheathing shall be designed to support all loads specified in this code and shall be capable of supporting concentrated loads of not less than 300 pounds (1334 N) without failure. The concentrated load shall be applied by a loaded disc, 3 inches (76 mm) or smaller in diameter. Structural roof sheathing shall meet the following requirement:

Deflection under uniform design live and dead load limited to 1/180 of the span between supporting rafters or beams and 1/240 under live load only.

Roof sheathing conforming to the provisions of Tables 23-I-R-1 and 23-I-R-2 or 23-I-S-1 and 23-I-S-2 or 23-I-S-3 shall be deemed to meet the requirements of this section.

Wood structural panel roof sheathing shall be bonded by intermediate or exterior glue. Wood structural panel roof sheathing exposed on the underside shall be bonded with exterior glue.