3:28:33 PM.
Address: /showpage.php~file=06260200.htm.html
Title: Section 2602 • Size: 14016
Go to Table of Contents
Go to previous section: 2601
Go to next section: 2603
2602.1 General. The provisions of this section shall govern the requirements and uses of foam plastic insulation in buildings and structures. For trim, see Section 601.5.5.
EXCEPTION: Foam plastic insulation when tested in a minimum thickness of 4 inches (102 mm) may be used in a greater thickness in cold-storage buildings, ice plants, food-processing rooms and similar areas. For rooms within a building, the foam plastic insulation shall be protected by a thermal barrier on both sides having an index of 15.
EXCEPTION: The thermal barrier is not required:
1. For siding backer board, provided the foam plastic
insulation is not of more than 2,000 Btu per square foot (22.7
MJ/) as determined by U.B.C. Standard
26-1 and when it is separated from the interior of the building
by not less than 2 inches (51 mm) of mineral fiber insulation
or equivalent, or applied as re-siding over existing wall construction.
2. For walk-in coolers and freezer units having an
aggregate floor area less than 400 square feet (37.2 ).
3. In a masonry or concrete wall, floor or roof system when the foam plastic insulation is covered by a minimum of 1-inch (25 mm) thickness of masonry or concrete. Loose-fill type foam plastic insulation shall be tested as board stock for flame spread and smoke development as described above.
4. Within an attic or crawl space where entry is made only for service of utilities, and when foam plastic insulation is covered with a material such as 1 1/2-inch-thick (38 mm) mineral fiber insulation, 1/4-inch-thick (6.4 mm) plywood, hardboard or gypsum wallboard, corrosion-resistant sheet metal having a base metal thickness not less than 0.0160 inch (0.4 mm) at any point, or other approved material installed in such a manner that the foam plastic insulation is not exposed.
5. In cooler and freezer walls when:
5.1 The foam plastic insulation has a flame-spread rating of 25 or less when tested in a minimum 4-inch (102 mm) thickness;
5.2 Has flash and self-ignition temperatures of not less than 600°F. and 800°F. (316°C. and 427°C.), respectively;
5.3 Is covered by not less than 0.032-inch (0.8 mm) aluminum or corrosion-resistant steel having a base metal thickness not less than 0.0160 inch (0.4 mm) at any point; and
5.4 Is protected by an automatic sprinkler system. When the cooler or freezer is within a building, both the cooler or freezer and that part of the building in which it is located shall be sprinklered.
2602.5.2 Noncombustible exterior walls.
1. The building is protected throughout with automatic sprinklers.
2. Foam plastic insulation tested in the maximum thickness and density intended for use, has a flame-spread rating of 25 or less and a smoke-developed rating of 450 or less in accordance with U.B.C. Standard 8-1.
3. The foam plastic insulation has a maximum 4-inch (102 mm) thickness.
4. The thermal barrier may be omitted when the foam plastic insulation is covered by not less than 0.032-inch-thick (0.8 mm) aluminum or corrosion-resistant sheet steel, having a base metal thickness of 0.0160 (0.4 mm) inch.
5. When the wall is required to have a fire-resistive rating, data based on tests conducted in accordance with U.B.C. Standard 7-1 are provided to substantiate that the required fire-resistive rating is maintained.
2602.5.2.2 Buildings of any height. Except for foam plastic insulation in masonry or concrete construction complying with Section 2602.4, Exception 3, assemblies employing foam plastic insulation in or on exterior walls of buildings where the exterior walls are required to be of noncombustible construction shall comply with the following:
1. When the wall is required to have a fire-resistive rating, data based on tests conducted in accordance with U.B.C. Standard 7-1, are provided to substantiate that the fire-resistive rating is maintained.
2. The foam plastic insulation is separated from the interior of the building by a thermal barrier having an index of 15 unless specifically approved under Section 2602.6.
3. Combustible content of foam plastic insulation
in any portion of the wall or panel does not exceed 6,000 Btu
per square foot (68.2 MJ/) of wall area
as determined by tests in accordance with U.B.C. Standard 26-1.
4. Foam plastic insulation, exterior coatings and facings tested separately, shall each have a flame-spread rating of 25 or less and a smoke-developed rating of 450 or less in accordance with U.B.C. Standard 8-1. The foam plastic shall be tested in the thickness intended for use.
5. The wall assembly is tested in accordance with U.B.C. Standard 26-4 and complies with the conditions of acceptance contained therein.
6. Foam plastic insulation is listed and the edge or face of each piece is labeled with the following information:
6.1 Inspection agency name.
6.2 Product for which the insulation is listed.
6.3 Identification of the insulation manufacturer.
6.4 Flame-spread and smoke-development classifications.
2602.5.3 Roofing. Foam plastic insulation meeting the requirements of Sections 2602.2, 2602.3 and 2602.4 may be used as part of a roof-covering assembly, provided the assembly with the foam plastic insulation is a Class A, B or C roof covering when tested in accordance with U.B.C. Standard 15-2. Foam plastic insulation which is a part of a Class A, B or C roof-covering assembly need not meet the requirements of Sections 2602.2, 2602.3 and 2602.4, provided the assembly with the foam plastic insulation satisfactorily passes a test for insulated roof decks.
Any roof covering installed in accordance with this code and the manufacturer's instructions may be applied over foam plastic insulation when the foam is separated from the interior of the building by plywood sheathing not less than 1/2 inch (12.7 mm) in thickness bonded with exterior glue, with edges supported by blocking, tongue-and-groove joints or other approved type of edge support, or an equivalent material. The thermal barrier requirement is waived.
For all roof applications, the smoke-developed rating shall not be limited.
Foam plastic insulation in a thickness greater than
4 inches (102 mm) may be used if it has been tested for flame
spread and smoke development at a minimum thickness of 4 inches
(102 mm) provided the end use has been specifically approved in
accordance with this subsection with the thickness and density
intended for use.
Go to Table of Contents
Go to previous section: 2601
Go to next section: 2603
Commercial Asbuilts: BOMA Asbuilt | Definitions | Projects | Project Types | FAQ | Useful links |
Residential Asbuilts: Projects | Asbuilt Services | FAQ |
Contact | Copyright | Privacy Policy | Site Map | News |