SECTION 3005 - ELEVATOR MACHINE ROOM

3005.1 Operation Solid-state Equipment. When solid-state equipment is used to operate the elevators, the elevator equipment room shall be provided with an independent ventilation or air-conditioning system to prevent the overheating of the electrical equipment. The operating temperature shall be established by the elevator equipment manufacturer's specification. When standby power is connected to elevators, the machine room ventilation or air conditioning shall be connected to standby.

3005.2 Detection. The elevator machine room serving a pressurized elevator hoistway shall be pressurized upon activation of a heat or smoke detector located in the elevator machine room. See Section 905, Smoke Control.