SECTION 3110 - DESIGN REQUIREMENTS

3110.1 Structural Systems. Structural systems of buildings or structures shall be constructed, connected and anchored to resist flotation, collapse or permanent lateral movement due to loads from flooding equal to the base flood elevation.

3110.2 Design Loads. The structural system shall be designed in accordance with well-established engineering principles and with consideration of hydrodynamic and hydrostatic loads. The required loading shall be established by site-specific criteria or approved national standards. Impact loads shall be considered in the analysis of the structural system.

3110.3 Load Combinations. Loading combinations shall be subject to approval by the building official. The structural system shall be designed to resist each combination of loading acting simultaneously. In lieu of site-specific loading requirements, load combinations from an approved national standard may be used.

3110.4 Stress Increases. Allowable stresses may be increased one third for flood loads in combination with dead load or dead and live load combinations. When strength design is used, flood loads may be considered as dead loads when considering dead and live load conditions. Flood loads may be considered as wind loads in other load combinations.

3110.5 Overturning. Buildings and structures and parts or elements shall be designed to resist sliding or overturning by at least 1.5 times the lateral force or overturning moment caused by wind and flood loads acting simultaneously. For the purpose of providing stability, only the dead load shall be considered effective in resisting overturning.

3110.6 Breakaway Walls. When walls or partitions located below the base flood elevation are required to break away in accordance with Section 3108.3, such walls shall be designed for not less than 10 pounds per square foot (psf) (0.48 kN/) or more than 20 psf (0.96 kN/) on the vertical projected area.