SECTION 3409 - BASEMENT ACCESS OR SPRINKLER PROTECTION

An approved automatic sprinkler system shall be provided in basements or stories exceeding 1,500 square feet (139.3 ) in area and not having a minimum of 20 square feet (1.86 ) of opening entirely above the adjoining ground level in each 50 lineal feet (15 240 mm) or fraction thereof of exterior wall on at least one side of the building. Openings shall have a minimum clear dimension of 30 inches (762 mm).

If any portion of a basement is located more than 75 feet (22 860 mm) from required openings, the basement shall be provided with an approved automatic sprinkler system throughout.