An approved automatic sprinkler system shall be provided
in basements or stories exceeding 1,500 square feet (139.3 )
in area and not having a minimum of 20 square feet (1.86
)
of opening entirely above the adjoining ground level in each 50
lineal feet (15 240 mm) or fraction thereof of exterior wall on
at least one side of the building. Openings shall have a minimum
clear dimension of 30 inches (762 mm).
If any portion of a basement is located more than
75 feet (22 860 mm) from required openings, the basement shall
be provided with an approved automatic sprinkler system throughout.